YOUR CURRENT POSITION: Home > CABLE & WIRE > Offshore & Marine Cable

MV RFOU P19/P21 12/20KV (NEK606) 

ApplicationsThese P19/P21 RFOU 12/20KV NEK606 Water Blocked Offshore Marine cables are partially water blocked, flame retardant, low smoke, halogen free and mud

Applications

These P19/P21 RFOU 12/20KV NEK606 Water Blocked Offshore Marine cables are partially water blocked, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power. Offshore power Medium Voltage cables. Medium voltage heavy duty, mud resistant cables for offshore applications. Halogen free, flame and fire non propagator. Excellent resistan-ce to oils, abrasion, petrochemical fluids, moisture and salt water. Based on IEC 60092-354 and NEK TS 606. Suitable for fixed installations in vessels and oil rigs.

Standards

IEC 60092
IEC 60332 
NEK 606 

Construction

Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.
Conductor Screen: Semi conducting material.
Insulation: Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).
Insulation Screen: Semi conducting material and tinned copper wire braid.
Filler: Water blocking fillers, if required.
Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.
Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.
Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.
Inner Sheath: Halogen free thermosetting compound, SHF2 (for TYPE P19), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P19/P21), coloured red.
Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.
 

Optional

P20 or P20/P22 RFOU/TFOU 18/30(36) kV.
 

Electrical Characteristics

NOMINAL CROSS SECTION AREA MM2 16 25 35 50 70 95
NOMINAL CONDUCTOR DIAMETER MM 5.2 6.5 7.4 8.7 10.3 12.2
MAXIMUM DC RESISTANT@20˚C O/KM 1.16 0.734 0.529 0.391 0.27 0.195
CONTINUOUS CURRENT RATING@45˚C1 CORE A 96 127 157 196 242 293
CONTINUOUS CURRENT RATING@45˚C3 CORE A 67 89 110 137 169 205
SHORT CIRCUIT CURRENT 1S A 2290 3580 5010 7150 10020 13590
OPERATING VOLTAGE KV 12/20 12/20 12/20 12/20 12/20 12/20
 
NOMINAL CROSS SECTION AREA MM2 120 150 185 240 300
NOMINAL CONDUCTOR DIAMETER MM 13.8 15.1 17.0 19.6 21.9
MAXIMUM DC RESISTANT@20˚C O/KM 0.154 0.126 0.1 0.0762 0.0607
CONTINUOUS CURRENT RATING@45˚C1 CORE A 339 389 444 522 601
CONTINUOUS CURRENT RATING@45˚C3 CORE A 237 272 311 365 421
SHORT CIRCUIT CURRENT 1S A 17170 21460 26470 34340 42930
OPERATING VOLTAGE KV 12/20 12/20 12/20 12/20 12/20
 
Ambient Temperature Correction Factors
AMBIENT TEMPERATURE CORRECTION FACTORS 35 40 45 50 55 60 65 70 75 80
RATING FACTOR 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Mechanical and Thermal Properties
Bending Radius :15×OD (during installation); 9×OD (fixed installed).
Temperature Range : -20˚C ~ +90˚C.
Dimensions and Weight
CONSTRUCTION NO. OF CORES×CROSS SECTION (MM2) NOMINAL INSULATION THICKNESS MM NOMINAL BEDDING THICKNESS MM NOMINAL INNER SHEATH THICKNESS MM NOMINAL OUTER SHEATH THICKNESS MM    
NOMINAL OVERALL DIAMETER MM NOMINAL WEIGHT KG/KM
1×16 5.5 1.4 1.2 1 30.0±2 1260
1×25 5.5 1.5 1.2 1.2 34.0±2 1607
1×35 5.5 1.8 1.3 1.2 34.7±2 1675
1×50 5.5 1.8 1.4 1.2 36.2±2 1885
1×70 5.5 1.9 1.4 1.2 37.0±2 2174
1×95 5.5 2 1.5 1.4 39.8±2 2594
1×120 5.5 2 1.5 1.4 41.6±2 2951
1×150 5.5 2.1 1.6 1.4 43.5±2 3407
1×185 5.5 2.2 1.6 1.4 45.7±2 3953
1×240 5.5 2.3 1.7 1.6 49.0±2 4736
1×300 5.5 2.4 1.8 1.6 51.7±2 5581
3×16 5.5 1.8 2 1 57.1±2 5198
3×25 5.5 1.9 2 1.2 64.6±2 5990
3×35 5.5 2.9 2.1 1.2 65.0±2 6290
3×50 5.5 3 2.2 1.2 67.8±2 7077
3×70 5.5 3.1 2.3 1.2 71.5±2 8180
3×95 5.5 3.3 2.4 1.4 75.8±2 9608
3×120 5.5 3.4 2.5 1.4 79.8±2 11109
3×150 5.5 3.6 2.6 1.4 84.7±2 12752
3×185 5.5 3.8 2.7 1.4 92.3±2 12878
3×240 5.5 4 2.9 1.6 99.3±2 15461
3×300 5.5 4.2 3 1.6 105.1±2 18050
 
Note: For XLPE insulated cable, a thinner insulation thickness is applied.
 

Contact Us, Now.
24-hour service hotline
Contact online customer service
Add: Factory :No.33 Zhengzhou City, Henan Province,China
Related products
Offshore & Marine Control Cables
RFOU(i) S2/S6 250V NEK606
RFOU(i) S1/S5 250V NEK606
BFOU(I) S3/S7 (NEK 606 )