EAYY 0.6/1kV Cable

EAYY 0.6/1kV Cable

Application: Austrian reference Low voltage power distribution cable. Suitability: For fixed installation. Can be used indoors, outdoors, in water or underground. Standards & Voltage Rating: HD 603 S1, HD 308 S2, OVE K 23, OVE K 603. Flame retardant to: IEC/EN 60332-1. 0.6/1kV.

Cable Description

The EAYY is a 0.6/1kV low voltage unarmoured power cable used  in a range of industries, including renewable energy and petrochemicals. The PVC insulation and sheath are ideal for where the cable may be exposed to changes in temperature. The PVC sheath is durable and offers protection against UV radiation and a resistance to chemicals including oils, acids and alkalis. The cable is flame retardant and can be used indoors, outdoors, in water or underground.
The EAYY cable has either class 1 solid sectorial (SE) or class 2 stranded round (RM) or sectorial (SM) Aluminium conductors. The lightweight nature of aluminium compared to that of a copper conductor, provides for easier handling during installation. The PVC (Polyvinyl Chloride) insulation and sheathing are ideal for applications where the cable may be exposed to high or low temperatures. The sheathing offers protection against UV radiation (Ultraviolet), helping to prevent degradation over the course of the cable lifespan. The PVC materials also provide chemical stability, a robust durability, and a resistance to chemicals including oils, acids and alkalis.
Flame retardant, the cable is also CPR compliant for fixed installation in accordance with EN-50575.

Standards

  • BS EN/IEC 60332-1
  • BS EN/IEC 60228
  • HD 308 S2
  • HD 603 S1
  • ÖVE/ÖNORM E 8200-603
  • ÖVE/ÖNORM E 8200-627

Construction

  • Conductor: Class 1 solid or class 2 stranded aluminium
  • Insulation: Polyvinyl Chloride (PVC)
  • Filler: Polyvinyl Chloride (PVC)
  • Outer Sheath: Polyvinyl Chloride (PVC)
  • Sheath Colour: Black

Key Features

Core Identification
HD 308 S2
Minimum Bending Radius
Single Core 15 x Overall Diameter
Multicore 12 x Overall Diameter
Temperature Limits
Temperature Range:
Fixed: -20°C to +70°C
Flexing: -5ºC to +70ºC
Maximum short circuit temperature:
300mm² and under: 160°C
Over 300mm²: 140°C
Voltage Rating
600/1000 Volts
Flame Retardancy
BS EN/IEC 60332-1

Cable Dimensions

Reference Conductor Size (mm2) No Of Cores Conductor Type Overall Diameter(mm) Weight(Kg/Km)
5X10 10 5 SOLID 21.0 425
1X16 16 1 SOLID 9.5 120
4X16 16 4 STRANDED 19 415
5X16 16 5 SOLID 23.0 525
1X25 25 1 STRANDED 11.5 175
4X25 25 4 STRANDED 24 890
5X25 25 5 STRANDED 27.0 1025
1X35 35 1 STRANDED 13.0 210
4X35 35 4 STRANDED 28 1075
5X35 35 5 STRANDED 31.0 1235
1X50 50 1 STRANDED 14.0 285
4X50 50 4 CLASS 2SECTORED 29 1020
5X50 50 5 STRANDED 34.5 1555
1X70 70 1 STRANDED 16.0 365
4X70 70 4 CLASS 2SECTORED 34.0 1315
5X70 70 5 STRANDED 39.5 2025
1X95 95 1 STRANDED 18.0 520
4X95 95 4 CLASS 2SECTORED 37.0 1700
5X95 95 5 STRANDED 46.0 2600
1X120 120 1 STRANDED 19.5 560
4X120 120 4 CLASS 2SECTORED 40.0 2465
5X120 120 5 STRANDED 49.0 3200
1X150 150 1 STRANDED 22.0 675
4X150 150 4 CLASS 2SECTORED 43.0 2600
5X150 150 5 STRANDED 56 4300
1X185 185 1 STRANDED 24.0 830
4X185 185 4 CLASS 2SECTORED 52.5 3790
5X185 185 5 STRANDED 61 5350
1X240 240 1 STRANDED 27.0 1065
4X240 240 4 CLASS 2SECTORED 55.0 4100
5X240 240 5 STRANDED 70 7600
1X300 300 1 STRANDED 30.0 1290
4X300 300 4 CLASS 2SECTORED 59.0 5000

Contact Us, Now.
24-hour service hotline
Contact online customer service
Add: Factory :No.33 Zhengzhou City, Henan Province,China
Related products
XHIO1RV 18/30kV Cable
XHIO1RV 18/30kV Cable
MCMK Cable
MCMK Cable
Single Core Medium Voltage Power Cable
Single Core Medium Voltage Power Cable
15-35KV MV-105 EPR/PVC Copper Tape Shield cable
Copper Single Conductor 15-35KV MV-105 EPR/PVC Copper Tape Shield cable