YOUR CURRENT POSITION: Home > CABLE & WIRE > Instrumentation cables

RE-2Y(st)Y Cables

RE-2Y(st)Y are PE insulated and PVC sheathed instrumentation cables manufactured in accordance with British and European standard BS EN 50288. These multi-eleme
BS EN 50288-7 - RE-2Y(ST)Y SWAY PVC CABLE
BS EN 50288-7 - RE-2Y(ST)Y SWAY PVC PIMF CABLE
RE-2Y(st)Y Cables
RE-2Y(st)Y are PE insulated and PVC sheathed instrumentation cables manufactured in accordance with British and European standard BS EN 50288. These multi-element metallic cables are designed for the signal transmission in instrumentation, analogue and digital communication, and control applications in process plants such as those found in the petrochemical and power generation industries.
This range of cables is particularly suitable for applications requiring the cable to withstand electromagnetic interference due to their protective screen - available as collective screening of PiMF / TiMF constructions. RE-2Y(st)Y are suitable for both fixed and mobile installations. Their low values of signal attenuation and low mutual capacitance enable signal transmission over long distances.RE-2Y(st)Y cables with a blue outer sheath are designed to be suitable for use in intrinsically safe systems. Those with a black outer sheath are UV resistant.This range of instrumentation cables has a maximum operating temperature rating of 75℃. They generally have a voltage rating of 300V, however we also supply 90V and 500V rated cables upon request.
Construction Table
  BS EN 50288-7 - RE-2Y(ST)Y SWAY PVC CABLE BS EN 50288-7 - RE-2Y(ST)Y SWAY PVC PIMF CABLE
VOLTAGE 300V
CONDUCTOR 0.5mm2 - 0.75mm2: Class 5 Flexible Stranded Copper

1mm2 and above: Class 2 Stranded Copper
INSULATION PE (Polyethylene)
INDIVIDUAL SCREEN - Al/PET (Aluminium/Polyester Tape)
COLLECTIVE SCREEN Al/PET (Aluminium/Polyester Tape)
INNER SHEATH PVC (Polyvinyl Chloride)
ARMOUR SWA (Galvanised Steel Wire)
OUTER SHEATH PVC (Polyvinyl Chloride)

Parameters
Cross Sections (mm2) Nominal Overall Diameter (mm) Approximate Weight (kg/km)
1x2x0,5 6 44
2x2x0,5 8.8 76
4x2x0,5 10.3 115
5x2x0,5 11.2 134
6x2x0,5 12.1 153
8x2x0,5 13.7 196
10x2x0,5 15.6 241
12x2x0,5 16.1 272
16x2x0,5 17.8 338
20x2x0,5 20 416
24x2x0,5 22.2 495
1x2x0,75 6.7 54
2x2x0,75 10 98
4x2x0,75 11.5 146
5x2x0,75 12.7 177
6x2x0,75 13.8 204
8x2x0,75 15.6 261
10x2x0,75 17.6 313
12x2x0,75 18.4 365
16x2x0,75 20.3 456
20x2x0,75 22.8 562
24x2x0,75 25.4 671
1x2x1 6.9 59
2x2x1 10.3 108
4x2x1 11.9 165
5x2x1 13.1 201
6x2x1 14.3 233
8x2x1 16.2 300
10x2x1 18.4 370
12x2x1 19 420
16x2x1 21.3 540
20x2x1 23.9 665
24x2x1 26.6 793
1x2x1,3 7.5 72
2x2x1,3 10.9 126
4x2x1,3 12.9 204
5x2x1,3 14 242
6x2x1,3 15.4 288
8x2x1,3 17.3 362
10x2x1,3 19.7 448
12x2x1,3 20.4 514
16x2x1,3 22.8 664
20x2x1,3 25.6 820
24x2x1,3 28.5 977
1x2x1,5 7.7 76
2x2x1,5 11.3 135
4x2x1,5 13.3 220
5x2x1,5 14.5 262
6x2x1,5 15.9 312
8x2x1,5 18.1 403
10x2x1,5 20.4 488
12x2x1,5 21.3 571
16x2x1,5 23.8 736
20x2x1,5 26.7 908
24x2x1,5 29.7 1083
1x2x2,5 8.9 103
2x2x2,5 13.4 193
4x2x2,5 15.9 324
5x2x2,5 17.3 387
6x2x2,5 19.1 461
8x2x2,5 21.7 597
10x2x2,5 24.7 738
12x2x2,5 25.6 853
16x2x2,5 28.6 1105
20x2x2,5 32.3 1380
24x2x2,5 36 1646
For more information on the RE-2Y(st)Y cable range please see the attached datasheets or consider our wider portfolio of EN 50288 standard cables including RE-Y(st)Y, RE-2X(st)Y, and RE-2X(st)H cables. 

Contact Us, Now.
24-hour service hotline
Contact online customer service
Add: Technology Building, Tongbai Road, Zhongyuan District, Zhengzhou, Henan, China.
Related products
600V Instrumentation Cable,Single & Multiple Twisted Pairs,Multiple Pairs or Triads Cable
NF M87-202 Instrumentation Cable
UL Style Tray Cables
300V Instrumentation Cable,Single Pair or Triad,Multiple Pairs or Triads Cable