LV ABC Aerial Bundled Cables ( SFS 2200)

APPLICATION It is preferred to use AER cables instead of uninsulated conductors at low voltage networks. AER cables are especially used at areas where the cost

APPLICATION

 It is preferred to use AER cables instead of uninsulated conductors at low voltage networks. AER cables are especially used at areas where the cost of underground networks are expensive and also for electrification of rural areas like villages.

TECHNICAL DATA

 Max Operating Temperature: 90°C
Max. short Circuit Temperature: 250°C (max. 5 sec.)
Rated voltage: 0.6/1kV
Cable Code: AER

CONSTRUCTION

 Solid or Stranded Aluminium Conductor
PE or XLPE Insulation
Messenger wire

ELECTRICAL SPECIFICATIONS

NUMBER OF
CONDUCTOR
CROSS SECTION
NSULATED    WIRES MESSENGER    WIRE FINISHED CABLE
CONDUCTOR SIZE NUMBER
OF
WIRES
DIAMETER
OF
CONDUCTOR
RESISTANCE
OF20℃
CURRENT
CARRYING
CAPACITY
NUMBER
OF
WIRES
CURRENT
CARRYING
CAPACITY
DIAMETER OF MESSENG WIRE MIN.TENSILE STRENGHT MAX
RESISTANCE
OF 20℃
APP MAX
BUNDLE
DIAMETER
APP.NET
WEIGHT
mm² mm² mm Ω/km A mm: A mm kN Ω/km mm kg/km
1x16+1x16+25 1x16 1 4.4 1.91 70 1x16 60 5.9 7.4 1.38 15 225
3x16+1x16+25 3x16   4.4 1.91 60 1x16 60 5.9 7.1 1.38 22 350
3x25+1x16+35 3x25 7 5.9 1.2 80 1x16 60 6.9 10.3 0.986 26 475
3x35+1x16+50 3x35 7 6.9 0.868 95 1x16 60 8x1 14.2 0.72 30 625
3x50+1x16+70 3x50 7 8.1 0.641 120 1x16 60 9.6 20.6 0.493 35 800
3x70+1x16+95 3x70 7 9.6 0.443 150 1x16 60 11.4 27.9 0.363 41 1100
4x16+1x16+25 4x16   4.4 1.91 60 1x16 60 5.9 7.4 1.38 25 410
4x25+1x16+35 4x25 7 5.9 1.2 80 1x16 60 6.9 10.3 0.986 30 610
4x35+1x16+50 4x35 7 6.9 0.868 95 1x16 60 8.1 14.2 0.72 34 810
4x50+1x16+70 4x50 7 8.1 0.641 120 1x16 60 9.63 20.6 0.493 40 1060
4x70+1x16+95 4x70 7 9.3 0.443 150 1x16 60 11.4 27.9 0.363 47 1420
 
NUMBER QF
CONDUCTOR
CROSS SECTION
INSULATED WIRES MESSENGER WIRE FINISHED CABLE
CONDUCTOR SIZE NUMBER
OF
WIRES
DLAMETER
OF
CONDUCTOR
RESISTANCE OF
20C
CURRENT
CARRYING
CAPACITY
NUMBER
OF
WIRES
CURRENT
CARRYING
CAPACITY
DIAMETER  OF  MESSENGER
WIRE
MIN,TENSLE STRENGHT MAX.
RESSTANCE
OF  20℃
APP MAX. BUNDLE
DIAMETER
APP.NET
WEIGHT
mm² mm² mm Ω/km A mm? A mm kN Ω/km mm kg/km
1x16+25 1x16   4.4 1.91 75 - - 5.9 7,4 1.38 15 140
1x25+35 1×25 7 5.9 1.2 10 - - 6.9 10.3 0.986 17 200
1x3.5+5 1x35 7 6.9 0.868 125 - - 8.1 14.2 0.72 20 275
3x16+25 3x16   4.4 1.91 70 - - 5.9 7.4 1.38 22 275
3x25+35 3x25 7 5.9 1.2 90 - - 6.9 10.3 0.986 26 400
3x35+50 3x35 7 6.9 0.868 115 - - 8.1 14.2 0.72 30 575
3x50+70 3x50 7 8.1 0.641 140 - - 9.6 20.6 0.493 35 750
3x70+95 3x70 7 9.6 0.443 180 - - 11.4 27.9 0.363 41 050
3x120+95 3x120 19 12.8 0.253 250 - - 11.4 27.9 0.363 47 550
4x16+25 4x16   4.4 1.91 70 - - 5.9 7.4 1.38 24 375
4x25+35 4x25 7 5.9 1.2 90 - - 6.9 10.3 0.986 28 500
4x35+50 4x35 7 6.9 0.868 115 - - 8.1 14.2 0.72 32 680
4x50+70 4x50 7 8.1 0.641 140 - - 9.6 20.6 0.493 38 900
 
NUMBER OF
CONDUCTOR
CROSS SECTION
NSULATED WIRES MESSENGER WIRE FINISHED CABLE
CONDUCTOR SIZE NUMBER
OF
WIRES
DIAMETER
OF
CONDUCIOR
RESISTANCE
QF
20℃
CURRENT CARRYING CAPACITY NUMBER
OF
WIRES
CURRENT CARRYING CAPACITY DIAMETER  OF  MESSENGER
WIRE
MIN.TENSILE STRENGHT MAX
RESISTANCE
OF20^C
APP MAX
BUNDLE
DIAMETER
APP.NET
WEIGHT
mm² mm² mm Q/km A mm² A mm kN Ω/km mm kg/km
3x120+2x1+670 3x120 19 12.8 0.253 300 2x16 - 10.2 20.6 0.50 46 1600
3x150+70 3x150 19 14.5 0.206 344   - 10.2 20.6 0.50 48 1680
3x150+1x1+670 3x150 19 14.5 0.206 344 1x16 60 10.2 20.6 0.50 48 1780
3x150+2x16+70 3x150 19 14.5 0206 344 2x16 - 10.2 20.6 0.50 48 1850
3x120+95 3x120 19 12.8 0.253 300   - 12.9 27.9 0.343 47 1500
3x120+1x16+95 3x120 19 12.8 0.253 300 1x16 60 12.9 27.9 0.343 47 1620
3x120+2x61+95 3x120 19 12.8 0.253 300 2x16 - 12.9 27.9 0.343 47 1680
3x150+95 3x150 19 14.5 0.206 344   - 12.9 27.9 0.343 49 1740
3x150+1x1+695 3x150 19 14.5 0.206 344 1×16 60 12.9 27.9 0.343 49 1880
3x150+2x16+95 3x150 19 14.5 0.206 344 2x16 - 12.9 27.9 0.343 49 1940
 
NUMBER OF
CONDUCTOR
CROSS SECTION
NSULATED WIRES MESSENGER WIRE FINISHED CABLE
CONDUCTOR SIZE NUMBER
OF
WIRES
DIAMETER
OF
CONDUCTOR
RESISTANCE
OF
20℃
CURRENT
CARRYING
CAPACITY
NUMBER
OF
WTRES
CURRENT
CARRYING
CAPACITY
DIAMETER  OF  MESSENGER
WIRE
MIN.TENSILE STRENGHT MAX
RESISTANCE  OF  20°℃
APP MAX
BUNDLE
DIAETER
APP.NET
WEIGHT
mm mm² mm ②/km A mm² A mm kN /km mm kg/km
2x16 2x16 7 4.6 1.91 93 - - - - - 15 132
2x25 2x25 7 5.9 1.20 122 - - - - - 18.5 200
2x35 2x35 7 6.9 0.868 129 - - - - - 22.0 280
2x50 2x50 7 8.1 0.641 158 - - - - - 24.0 370
4x16 4x16 7 4.6 1.91 83 - - - - - 18.0 265
4x25 4x25 7 5.9 x20 111 - - - - - 22,0 400
4x35 4x35 7 6.9 0.868 131 - - - - - 26.0 550
3x25+54.6 3x25 7 5.9 1.20 112 - - 9.6 6.0 0.63 30.0 470
3x25+1x16+54.6 3x25 7 5.9 1.20 112 x16 60 9.6 16.0 0.63 30.0 570
3x25+2x16+54.6 3x 25 7 5.9 1.20 112 2x16   9.6 6.0 0.63 30.0 640
3x35+54.6 3x35 7 6.9 0.86 138 - - 9.6 16.0 0.63 33.0 580
3x3S+1x16+54.6 3x35 7 6.9 0.868 138 x16 60 9.6 6.0 63 33.0 690
3x35+2x16+54.6 3x35 7 6.9 0.868 138 2x16 - 9.6 16.0 0.63 33.0 750
3x50+54.6 3x50 7 8.1 0.641 168 - - 9.6 16.0 0.63 36,0 720
3x50+1x16+54.6 3x50 7 8.1 0.641 168 x16 60 9.6 16.0 0.63 36.0 820
3x50+2x16+54.6 3x5 7 8.1 0.641 168 2x16 - 9.6 6.0 0.63 36.0 890
3x70+54.6 3x70 12 9.7 0.443 213 - - 9.6 16.0 0.63 38.0 930
2x70+1x16+54.6 3x70 12 9.7 0.443 213 x16 60 9.6 6.0 0.63 38.0 030
3x70+2x16+54.6 3x70 12 9.7 0.443 213 2x16 - 9.6 16.0 0.63 38.0 100
3x70+1x25+54.6 3x70 12 9.7 0,443 213 x25 - 9.6 16.0 0.63 40.0 070
3x70+2x25+54.6 3x70 12 9.7 0.443 213 2x25 - 9.6 16.0 0.63 40.0 170
3x70+70 3x70 12 9.7 0,443 213 - - 10.2 20.6 0.50 41,.0 970
3x70+1x16+70 3x70 12 9.7 0.443 213 x16 60 0.2 20.6 0.50 41.0 080
3x70+2x16+70 3x70 12 9.7 0,443 213 2x16 - 0.2 20.6 0.50 41.0 150
3x95+70 3x95 19 1.5 0.320 258 - - 0.2 20.6 0.50 44,0 1200
3x95+1x16+70 3x95 19 11.5 0.320 258 x16 60 0.2 20.6 0.50 44,0 300
3x95+2x16+70 3x95 19 11.5 0.320 258 2x16 - 0.2 20.6 0.50 44,0 380
3x120+70 3x120 19 12.8 0.25 300 - - 0.2 20.6 0.50 46.0 430
 
 

Contact Us, Now.
24-hour service hotline
Contact online customer service
Add: Technology Building, Tongbai Road, Zhongyuan District, Zhengzhou, Henan, China.
Related products
CAAI CAAI-S Self-Supporting Cable (ICEA S-76-474)
Aerial Bundled Cables (DES/LVC/ABC Specification)
LV ABC Aerial Bundled Cables (TNB Specification)
Duplex Triplex Quadruplex Service Drop Cable