Saudi Arabia-Fire-Resistant Armored Cables for Data Centers
Release time: 2025-08-12

Saudi Arabia – Fire-Resistant Armored Cables for Data Centers

With Saudi Arabia’s rapid expansion of digital infrastructure under the Vision 2030 program, there has been a surge in data center construction led by both government agencies and private operators such as STC, Mobily, Aramco, and Hyperscale developers (Google, Oracle, Huawei Cloud).

In 2023–2024, Uni-Cable supplied fire-resistant low-voltage and medium-voltage armored power cables for multiple Tier III and Tier IV data centers in Riyadh and Jeddah. The key requirement was uninterrupted power supply during fire emergencies, ensuring compliance with Uptime Institute standards and Saudi Civil Defense fire codes.

Products Supplied

Fire-Resistant LV Power Cables

  • Type: Cu/Mica Tape/XLPE/LSZH + SWA (Steel Wire Armored)

  • Voltage Rating: 0.6/1kV

  • Core Options: 2C, 3C, 3.5C, 4C

  • Conductor Sizes: 2.5 mm² – 500 mm²

  • Fire Resistance: IEC 60331 (Circuit integrity under fire, 750°C – 950°C for 3 hours)

  • Flame Retardance: IEC 60332-3

  • Smoke & Toxicity: LSZH sheath meeting IEC 61034 & IEC 60754

Medium Voltage Fire-Survival Cables

  • Type: Cu/XLPE/Mica Tape/CWS/LSZH + SWA

  • Voltage Rating: 6.35/11kV and 12/20kV

  • Conductor Sizes: 70 mm² – 400 mm²

  • Special Feature: Maintains circuit integrity during 950°C fire + water spray test (BS 8491)

Control & Instrumentation Cables

  • Type: Cu/XLPE/LSZH Screened Pairs (Fire Resistant)

  • Pair Count: 2–48 pairs

  • Application: SCADA, HVAC, fire alarm, and BMS (Building Management Systems)

Application Areas

The supplied cables were installed for:

  • Critical UPS power feeds to server racks

  • MV supply lines between backup generators and substations

  • Essential safety systems (fire pumps, smoke extraction fans, emergency lighting, alarm circuits)

  • Control cabling for automation and monitoring

By using Uni-Cable’s fire-resistant armored cables, data centers ensured power continuity during fire incidents, enabling safe evacuation and protecting expensive IT assets.

Engineering Solutions

Uni-Cable provided customized solutions for Saudi projects:

  • Double armored versions for underground routing within data halls

  • Red LSZH sheath for easy identification of fire-survival circuits

  • Meter marking and RFID tagging for installation tracking

  • Pre-terminated kits with glands and lugs to reduce downtime during installation

Quality Inspection & Standards

International Standards

  • IEC 60331 / BS 6387 (Fire resistance – 750°C to 950°C, 3h)

  • IEC 60332-3 (Flame spread)

  • IEC 61034 (Smoke density)

  • IEC 60754 (Halogen acid gas emission)

  • IEC 60502-1/2 (LV & MV power cables)

Tests Conducted

  • Fire resistance test (950°C, with shock & water spray)

  • High voltage withstand (3.5kV / 15kV depending on type)

  • Insulation resistance & partial discharge test

  • Mechanical bending and armor adhesion

  • Aging and UV resistance test (for external runs)

A third-party inspection was carried out by Bureau Veritas Saudi Arabia, with factory witness testing before shipment.

Export & Logistics

  • Packaging: Heavy-duty steel-reinforced wooden drums with fire-safety labeling

  • Markings: Cable type, fire-resistance rating, batch number, Uni-Cable logo

  • Port of Loading: Shanghai Port

  • Destination Port: Jeddah Islamic Port & King Abdulaziz Port (Dammam)

  • Lead Time: 6 weeks including factory inspection

Uni-Cable Advantage

Compliant with Saudi Civil Defense fire codes
Proven performance in Tier III/Tier IV data centers
Complete cable system (power, control, fire alarm, accessories) supplied from one source
High stock availability for urgent projects
Technical documentation + support for consultants and EPC contractors

Project Impact

By supplying fire-resistant armored cables, Uni-Cable helped data centers in Saudi Arabia achieve:

  • Uptime Institute Tier IV certification readiness

  • Civil Defense compliance approval without design delays

  • Enhanced resilience against fire-related risks

  • Reduced downtime during installation due to customized lengths and accessories

Contractors praised the ease of installation and excellent documentation, while end-users highlighted the reliability and safety of Uni-Cable cables during fire-safety commissioning tests.