Application
The aerial bundled cables designed for overhead distribution lines have an insulated neutral messenger made of AAAC, over which the insulation aluminum phase conductors are helically wound. Can be used for fixed installation as overhead power lines up to 1000 V incl.Standard
TNB Specification IEC 60502Construction
PHASE CONDUCTOR: H68 condition aluminum conductor, round stranded compressed.NEUTRAL OR MESSENGER CONDUCTOR: Alloy aluminum conductor, round stranded compressed.
STREET LIGHTING CONDUCTOR: H68 condition aluminum conductor, round stranded compressed.
INSULATION: PE.
ASSEMBLY: The cable consists of insulated phase and street lighting aluminum conductors, which shall be held firmly onto the insulated neutral messenger aluminum alloy conductor in a right-hand (Z) lay.
Dimensions
NUMBER OF CORES X NOMINAL CROSS SECTION | MIN. BREAKING LOAD OF CONDUCTOR STRAND | CURRENT RATING IN THE AIR | OUTER DIAMETER | TOTAL WEIGHT |
MM² | KN | A | MM | KG/KM |
1x16+1x 25 RM | 6.4 | 61 | 15.3 | 160 |
3x16+1x 25 RM | 6.4 | 61 | 19.0 | 290 |
3x25+1x 25 RM | 6.4 | 84 | 23.2 | 400 |
3x35+1x 25 RM | 6.4 | 104 | 25.6 | 500 |
3x50+1x 35 RM | 8.9 | 129 | 30.0 | 680 |
3x70+1x 50 RM | 12.1 | 167 | 34.9 | 920 |
3x95+1x 70 RM | 18.0 | 209 | 40.6 | 1270 |
3x120+1x 70 RM | 18.0 | 246 | 44.1 | 1510 |
3x150+1x 95 RM | 24.2 | 283 | 49.2 | 1870 |
3x185+1x120 RM | 30.8 | 332 | 54.9 | 2340 |
3x25+1x25+1x16 RM | 6.4 | 84 | 23.2 | 470 |
3x35+1x25+1x16 RM | 6.4 | 104 | 25.6 | 560 |
3x50+1x35+1x16 RM | 8.9 | 129 | 30.0 | 740 |
3x70+1x50+1x16 RM | 12.1 | 167 | 34.9 | 980 |
3x95+1x70+1x16 RM | 18.0 | 209 | 40.6 | 1330 |
3x120+1x70+1x16 RM | 18.0 | 246 | 44.1 | 1580 |
3x150+1x95+1x16 RM | 24.2 | 283 | 49.2 | 1940 |
3x185+1x120+1x16 RM | 30.8 | 332 | 54.9 | 2410 |
other cross-sections on request